
26
Current: The current of the utility power supplied to the UPS.
Power Factor: The radio of the real power flowing to the UPS, to the apparent power of utility power. In an UPS
system, a UPS with a low power factor draws more current than a UPS with a high power factor for the same
amount of useful power transferred.
Bypass
Status: Displays the present status of bypass circuit. In bypass mode, the UPS will provide the power from bypass
input to the connected equipment directly.
Normal: The power quality of bypass circuit is normal.
Blackout: There is no input power being supplied in bypass circuit.
Over Voltage: The input voltage of bypass is higher than an acceptable threshold.
Under Voltage: The input voltage of bypass is lower than an acceptable threshold.
Frequency Failure: The frequency of bypass is out of tolerance.
Power Failure: The power of bypass is not qualify due to other power noise and distorted conditions.
Wrong Phase Sequence: The sequence of phases in bypass is different than utility input.
Overload: Output power consumption exceeds the power rating of UPS.
Extended Overload: The duration of overload has expired.
Voltage: The voltage of the bypass supplied to the UPS.
Current: The current of the bypass supplied to the UPS.
Frequency: The frequency of the bypass supplied to the UPS.
Power Factor: The radio of the real power flowing to the bypass, to the apparent power of bypass. In an UPS
system, a load with a low power factor draws more current than a load with a high power factor for the same
amount of useful power transferred.
Output
Status: Displays the present status of the output power the UPS is supplying to connected equipment.
Normal: The output power is normal.
Bypass: The UPS has switched to bypass mode and the utility power is being supplied directly to the
connected equipment bypassing the UPS circuitry.
Note: Bypass mode is only applicable in Online Series UPS units.
No Output: There is no output from the UPS. The UPS is switched off.
Short Circuit: There is a short circuit on the UPS output. This causes the UPS to stop supplying output power.
Boost: The utility voltage is below the regular voltage range. The UPS is increasing the output voltage closer
to normal.
Buck: The utility voltage is beyond the regular voltage range. The UPS is decreasing the output voltage
closer to normal.
Note: The Boost and Buck function are only available on a UPS with AVR; only high-end units with AVR have
a Buck feature. The UPS uses the AVR function to improve the utility voltage and supplies the power to its
connected equipment within a narrow range.
Overload: The present load exceeds the load threshold of the UPS. Remove some equipment from the UPS
to reduce the load.
Commenti su questo manuale